Excellent Corrosion Inhibition Water Treatment Plant Chemicals Power Plant Cooling Tower
Product Details:
Place of Origin: | China |
Brand Name: | B&W |
Certification: | ISO 9001:2008 ISO 14001:2004 |
Model Number: | XT - 604 |
Payment & Shipping Terms:
Minimum Order Quantity: | As Need |
---|---|
Price: | Negotiable |
Packaging Details: | In 200L drum |
Delivery Time: | 2 Weeks |
Payment Terms: | T/T, L/C |
Supply Ability: | 5000 MT |
Detail Information |
|||
Appearance: | Liquid | Purity: | 22% Min |
---|---|---|---|
Density: | 1.10 Min | PH: | 3.0±1.5 |
UN No.: | None | ||
High Light: | water treatment chemicals,water treatment liquid |
Product Description
Excellent Corrosion Inhibition Water Treatment Plant Chemicals Power Plant Cooling Tower
Scale and Corrosion Inhibitor XT - 604 Water Treatment Agent Liquid For Power Plant Cooling Tower
Description
Commodity: Scale and Corrosion Inhibitor XT - 604
Appearance: Liquid
Molecular Formula: --
Molecular Weight: --
CAS No.: --
Class: --
UN No.: --
Package and Storage
200L drum, IBC, Or per requested. Storage for six months in shady room and dry places.
Features
XT-604 is built with organophosphoric acid, polycarboxylic acid, carbon steel and copper corrosion inhibitor.
XT-604 can effectively chelate and disperse calcium carbonate, calcium sulfate and calcium phosphate scales.
XT-604 has excellent corrosion inhibition on carbon steel and copper.
XT-604 is mainly used in circulating cool water systems of power plants, chemical plants, petrochemical, steel & iron plants. It has the advantages of effective and strong scale and corrosion inhibition.
Specification
Items | Index |
Solid content % | 22.0 min |
Thiazole(C6H5N3) % | 2.0 min |
Total phosphoric acid (as PO43-) % | 6.8 min |
Phosphoric acid (as PO43-) % | 0.75 max |
Phosphorous acid (as PO33-)% | 2.25 max |
Density 20℃ (g/cm3) | 1.10 min |
PH (1% water solution) | 3.0±1.5 |
Usage and Dosage
Dosage of 5-20ppm is preferred (according to quantity of makeup water).
First Aid Measures
Inhalation
If inhaled, move patient to fresh air. If breathing stops, give artificial respiration.
Skin contact
Rinse with soap and plenty of water.
Eye contact
Rinse eyes with water as a precaution.
Ingestion
Don't feed unconscious people through the mouth. Rinse mouth with water.
Fire Fighting Measures
Extinguishing media
Fire extinguishing method and extinguishing agent
Use water fog, anti-ethanol foam, dry powder or carbon dioxide to extinguish the fire.
Special hazards from this substance or mixture
Hydrogen chloride gas, Potassium oxide
Advice to Fire Fighters
Wear self-contained breathing apparatus for fire fighting if necessary.
Acceidental Release Measures
Workers' protective measures, protective equipment and emergency procedures
Avoid breathing vapors, fumes, or gases.
Environmental Protection Measures
Do not let the product enter the sewer.
Methods for containment and removal of leaked chemicals and disposal materials used
Place in a suitable closed container for disposal.